Technical data | BC5150 |
---|---|
Number of Bus Terminals | 64 (255 with K-bus extension) |
Max. number of bytes fieldbus | 16 Tx/Rx PDOs |
Max. number of bytes process image | 512 byte input and 512 byte output |
Digital peripheral signals | 2,040 inputs/outputs |
Analog peripheral signals | 1024 inputs/outputs |
Data transfer rates | automatic detection up to 1 Mbaud |
Bus interface | open style connector, 5-pin |
Serial interface | programming and configuration interface |
Configuration | via KS2000 or fieldbus |
Power supply | 24 V DC (-15 %/+20 %) |
Input current | 60 mA + (total K-bus current)/4 |
Current supply K-bus | 1750 mA |
Power contacts | max. 10 A |
Electrical isolation | 500 V (power contact/supply voltage) |
Weight | approx. 100 g |
Operating/storage temperature | -25…+60 °C/-40…+85 °C |
Relative humidity | 95 %, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos. | IP 20/variable |
Approvals/markings | CE, UL, ATEX |
Ex marking | II 3 G Ex nA IIC T4 Gc |