Technical data | EPP3204-0002 |
---|---|
Protocol | EtherCAT |
Bus interface | 2 x M8 socket, shielded, screw type, P-coded |
Number of inputs | 4 |
Connection method | screw type M12 for 2-, 3- and 4-wire connections, presetting: 2-wire |
Sensor types | Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000 resistance measurement (e.g. potentiometer, 10 ?…1.2/4 k?) |
Signal type | Pt100 |
Measuring range | -200…+850 °C (Pt sensors); -60…+250 °C (Ni sensors) |
Resolution | 0.1 °C per digit |
Measuring error | < ±0.5 °C (Pt sensors in 4-wire connection) |
Conversion time | 800 ms up to 2 ms, see documentation, default: approx. 85 ms |
Nominal voltage | 24 V DC (-15 %/+20 %) |
Distributed clocks | – |
Measuring current | typ. 0.5 mA |
Input filter | 5 variations, configurable |
Sensor supply | – |
Current consumption from US | typ. 100 mA |
Electrical isolation | 500 V |
Special features | open-circuit recognition |
Operating/storage temperature | -25…+60 °C/-40…+85 °C |
Weight | approx. 165 g |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos. | IP 65/66/67 (conforms to EN 60529)/variable |
Approvals/markings | CE, UL |