Product characteristics | |||||
---|---|---|---|---|---|
Number of inputs and outputs | Number of relay outputs: 1 | ||||
Process connection | Ø 23 mm | ||||
Application | |||||
Medium temperature [°C] | -10…50 | ||||
Pressure rating [bar] | 1 | ||||
Electrical data | |||||
Operating voltage [V] | 80…250 AC / 90…250 DC | ||||
Max. power consumption [VA] | 3 | ||||
Min. insulation resistance [MΩ] | 100; (500 V DC) | ||||
Reverse polarity protection | no | ||||
Power-on delay time [s] | 60 | ||||
Inputs / outputs | |||||
Number of inputs and outputs | Number of relay outputs: 1 | ||||
Outputs | |||||
Output signal | switching signal | ||||
Number of relay outputs | 1 | ||||
Contact rating | 3 A (30 V DC / 250 V AC) | ||||
Switching function flow monitoring | relay energised when flow is present | ||||
Short-circuit proof | no | ||||
Overload protection | no | ||||
Measuring/setting range | |||||
Gases | |||||
Setting range [cm/s] | 100…1000 | ||||
Greatest sensitivity [cm/s] | 100…400 | ||||
Accuracy / deviations | |||||
Temperature gradient [K/min] | 5 | ||||
Response times | |||||
Response time [s] | 3…60 | ||||
Gases | |||||
Response time [s] | 3…60 | ||||
Software / programming | |||||
Adjustment of the switch point | potentiometer | ||||
Operating conditions | |||||
Ambient temperature [°C] | -10…50 | ||||
Storage temperature [°C] | -25…85 | ||||
Max. relative air humidity [%] | 90 | ||||
Protection | IP 65 | ||||
Mechanical data | |||||
Weight [g] | 209 | ||||
Dimensions [mm] | Ø 23 / L = 142 | ||||
Materials | housing: PBT; sensor surface: titanium | ||||
Materials (wetted parts) | PBT; titanium | ||||
Process connection | Ø 23 mm | ||||
Displays / operating elements | |||||
Display |
| ||||
Electrical connection | |||||
Required protection | miniature fuse to IEC60127-2 sheet 1; ≤ 5 A; fast acting | ||||
Accessories | |||||
Accessories (supplied) |
| ||||
Remarks | |||||
Remarks |
| ||||
Pack quantity | 1 pcs. | ||||
Electrical connection | |||||
Connection | Cable: 2 m, PUR; 4 x 0.5 mm² |