Product characteristics | |||||||||
---|---|---|---|---|---|---|---|---|---|
Output signal | switching signal; analogue signal; (configurable) | ||||||||
Measuring range |
| ||||||||
Process connection | threaded connection G 1/4 internal thread | ||||||||
Application | |||||||||
Special feature | Gold-plated contacts | ||||||||
Application | for industrial applications | ||||||||
Media | liquids and gases | ||||||||
Conditionally suitable for | use in gases at pressures > 25 bar only on request | ||||||||
Cannot be used for | oils | ||||||||
Medium temperature [°C] | -25…80 | ||||||||
Min. bursting pressure |
| ||||||||
Pressure rating |
| ||||||||
Type of pressure | relative pressure | ||||||||
Electrical data | |||||||||
Operating voltage [V] | 18…36 DC; (according to EN 50178 SELV/PELV) | ||||||||
Current consumption [mA] | < 50 | ||||||||
Min. insulation resistance [MΩ] | 100; (500 V DC) | ||||||||
Protection class | III | ||||||||
Reverse polarity protection | yes | ||||||||
Overvoltage protection | yes; (< 40 V) | ||||||||
Power-on delay time [s] | 0.3 | ||||||||
Integrated watchdog | yes | ||||||||
Inputs / outputs | |||||||||
Number of inputs and outputs | Number of digital outputs: 1; Number of analogue outputs: 1 | ||||||||
Outputs | |||||||||
Total number of outputs | 2 | ||||||||
Output signal | switching signal; analogue signal; (configurable) | ||||||||
Electrical design | PNP | ||||||||
Number of digital outputs | 1 | ||||||||
Output function | normally open / normally closed; (parameterisable) | ||||||||
Max. voltage drop switching output DC [V] | 2 | ||||||||
Permanent current rating of switching output DC [mA] | 250 | ||||||||
Switching frequency DC [Hz] | < 170 | ||||||||
Number of analogue outputs | 1 | ||||||||
Analogue current output [mA] | 4…20 | ||||||||
Max. load [Ω] | 500 | ||||||||
Analogue voltage output [V] | 0…10 | ||||||||
Min. load resistance [Ω] | 2000 | ||||||||
Short-circuit protection | yes | ||||||||
Type of short-circuit protection | pulsed | ||||||||
Measuring/setting range | |||||||||
Measuring range |
| ||||||||
Set point SP |
| ||||||||
Reset point rP |
| ||||||||
In steps of |
| ||||||||
Factory setting |
| ||||||||
Accuracy / deviations | |||||||||
Switch point accuracy [% of the span] | < ± 0,5 | ||||||||
Repeatability [% of the span] | < ± 0,1; (with temperature fluctuations < 10 K) | ||||||||
Characteristics deviation [% of the span] | < ± 0,25 (BFSL) / < ± 0,5 (LS); (BFSL = Best Fit Straight Line; LS = limit value setting) | ||||||||
Hysteresis deviation [% of the span] | < ± 0,25 | ||||||||
Long-term stability [% of the span] | < ± 0,05; (per 6 months) | ||||||||
Temperature coefficient zero point [% of the span / 10 K] | 0,2; (0…80 °C) | ||||||||
Temperature coefficient span [% of the span / 10 K] | 0,2; (0…80 °C) | ||||||||
Response times | |||||||||
Delay time programmable dS, dr [s] | 0; 0,2…50 | ||||||||
Max. response time analogue output [ms] | 3 | ||||||||
Software / programming | |||||||||
Parameter setting options | hysteresis / window; normally open / normally closed; switch-on/switch-off delay; Damping; Display unit; current/voltage output | ||||||||
Operating conditions | |||||||||
Ambient temperature [°C] | -20…80 | ||||||||
Storage temperature [°C] | -40…100 | ||||||||
Protection | IP 67 | ||||||||
Mechanical data | |||||||||
Weight [g] | 262.5 | ||||||||
Materials | stainless steel (1.4301 / 304); stainless steel (1.4404 / 316L); PC; PBT; PEI; FKM | ||||||||
Materials (wetted parts) | stainless steel (1.4404 / 316L); ceramics; sealing of the measuring cell: EPDM | ||||||||
Min. pressure cycles | 100 million | ||||||||
Process connection | threaded connection G 1/4 internal thread | ||||||||
Displays / operating elements | |||||||||
Display |
| ||||||||
Remarks | |||||||||
Pack quantity | 1 pcs. | ||||||||
Electrical connection | |||||||||
Connection | Connector: 1 x M12; Contacts: gold-plated |