Product characteristics | |||
---|---|---|---|
Output function | normally open / normally closed; (selectable) | ||
Sensing range [mm] | 5…40; (programming buttons) | ||
Housing | threaded type | ||
Dimensions [mm] | M30 x 1.5 / L = 90 | ||
Application | |||
Installation | detection through non-metallic container wall or on bypass pipes | ||
Media | dry bulk material; liquids | ||
Electrical data | |||
Frequency AC [Hz] | 47…63 | ||
Operating voltage [V] | 30…250 AC / 20…250 DC | ||
Protection class | II | ||
Reverse polarity protection | yes | ||
Outputs | |||
Output function | normally open / normally closed; (selectable) | ||
Max. voltage drop switching output DC [V] | 8 | ||
Max. voltage drop switching output AC [V] | 10 | ||
Max. leakage current [mA] | 2.5 (250 V AC) / 1.7 (110 V AC) / 1.5 (24 V DC) | ||
Permanent current rating of switching output AC [mA] | 100; (150 (…40 °C)) | ||
Permanent current rating of switching output DC [mA] | 100; (150 (…40 °C)) | ||
Short-time current rating of switching output [mA] | 1000; (20 ms / 0,5 Hz) | ||
Switching frequency AC [Hz] | 10 | ||
Switching frequency DC [Hz] | 10 | ||
Short-circuit proof | no | ||
Overload protection | no | ||
Detection zone | |||
Sensing range [mm] | 5…40; (programming buttons) | ||
Sensing range adjustable | yes | ||
Factory setting sensing range [mm] | 20 | ||
Real sensing range Sr [mm] | 20 ± 10 % | ||
Accuracy / deviations | |||
Correction factor | glass: 0.3 / water: 1 / ceramics: 0.2 / PVC: 0.1 | ||
Hysteresis [% of Sr] | 1…15 | ||
Switch point drift [% of Sr] | -20…20 | ||
Operating conditions | |||
Ambient temperature [°C] | -25…80 | ||
Note on ambient temperature |
| ||
Protection | IP 65; IP 67 | ||
Mechanical data | |||
Weight [g] | 109.8 | ||
Housing | threaded type | ||
Mounting | non-flush mountable | ||
Dimensions [mm] | M30 x 1.5 / L = 90 | ||
Thread designation | M30 x 1.5 | ||
Materials | housing: PBT; plug: PC; pushbuttons: TPE-U | ||
Displays / operating elements | |||
Display |
| ||
Teach function | yes | ||
Electronic lock | yes | ||
Electrical connection | |||
Required protection | miniature fuse to IEC60127-2 sheet 1; ≤ 2 A; fast acting | ||
Accessories | |||
Accessories (supplied) |
| ||
Remarks | |||
Remarks |
| ||
Pack quantity | 1 pcs. | ||
Electrical connection – plug | |||
Connector: 1 x 1/2″ |