Product characteristics | ||||
---|---|---|---|---|
Electrical design | NAMUR | |||
Output function | 2 x normally closed | |||
Sensing range [mm] | 4 | |||
Housing | rectangular | |||
Dimensions [mm] | 40 x 26 x 60 | |||
Application | ||||
Application | for actuators using standard ISO 5211 (VDI/VDE ) mounting | |||
Electrical data | ||||
Connection to switching amplifiers | yes | |||
Switching amplifiers | connection to certified intrinsically safe circuits with the max. values: U = 15 V / I = 50 mA / P = 120 mW | |||
Nominal voltage DC [V] | 8.2; (1kΩ) | |||
Current consumption [mA] | < 1; (disabled; conductive: > 2,2) | |||
Protection class | III | |||
Outputs | ||||
Electrical design | NAMUR | |||
Output function | 2 x normally closed | |||
Switching frequency DC [Hz] | 250 | |||
Detection zone | ||||
Sensing range [mm] | 4 | |||
Real sensing range Sr [mm] | 4 ± 10 % | |||
Accuracy / deviations | ||||
Correction factor | steel: 1 / stainless steel: 0.7 / brass: 0.5 / aluminium: 0.4 / copper: 0.3 | |||
Hysteresis [% of Sr] | 1…15 | |||
Switch point drift [% of Sr] | -10…10 | |||
Operating conditions | ||||
Ambient temperature [°C] | -20…70 | |||
Protection | IP 67 | |||
Safety classification | ||||
Max. internal capacitance [nF] | 150; (per intrinsically safe circuit) | |||
Max. internal inductance [µH] | 150; (per intrinsically safe circuit) | |||
Mechanical data | ||||
Weight [g] | 175 | |||
Housing | rectangular | |||
Mounting | non-flush mountable | |||
Dimensions [mm] | 40 x 26 x 60 | |||
Materials | housing: PBT; cover: PC | |||
Displays / operating elements | ||||
Display |
| |||
Remarks | ||||
Remarks |
| |||
Pack quantity | 1 pcs. | |||
Electrical connection – plug | ||||
Connection | Connector: Rd24 | |||
Electrical connection – socket | ||||
Connector: 1 x M12 |