Product characteristics | |||
---|---|---|---|
Electrical design | NAMUR | ||
Output function | normally closed | ||
Sensing range [mm] | 35 | ||
Housing | rectangular | ||
Dimensions [mm] | 40 x 40 x 66 | ||
Electrical data | |||
Connection to switching amplifiers | yes | ||
Switching amplifiers | connection to certified intrinsically safe circuits with the max. values: U = 15 V / I = 50 mA / P = 120 mW | ||
Nominal voltage DC [V] | 8.2; (1kΩ) | ||
Supply voltage DC [V] | 7.5…30; (when used outside the hazardous area) | ||
Current consumption [mA] | < 1; (disabled; conductive: > 2,1) | ||
Protection class | III | ||
Outputs | |||
Electrical design | NAMUR | ||
Output function | normally closed | ||
Permanent current rating of switching output DC [mA] | 30; (when used outside the hazardous area) | ||
Switching frequency DC [Hz] | 100 | ||
Detection zone | |||
Sensing range [mm] | 35 | ||
Real sensing range Sr [mm] | 35 ± 10 % | ||
Accuracy / deviations | |||
Correction factor | steel: 1 / stainless steel: 0.7 / brass: 0.5 / aluminium: 0.4 / copper: 0.3 | ||
Hysteresis [% of Sr] | 1…15 | ||
Switch point drift [% of Sr] | -10…10 | ||
Operating conditions | |||
Ambient temperature [°C] | -20…70 | ||
Protection | IP 67 | ||
Safety classification | |||
Max. internal capacitance [nF] | 220 | ||
Max. internal inductance [µH] | 710 | ||
Mechanical data | |||
Weight [g] | 189.5 | ||
Housing | rectangular | ||
Mounting | non-flush mountable | ||
Dimensions [mm] | 40 x 40 x 66 | ||
Materials | housing: PPE; end cap: PPS; connector housing: brass special coating; mounting adapter: PPS | ||
Displays / operating elements | |||
Display |
| ||
Accessories | |||
Accessories (supplied) |
| ||
Remarks | |||
Remarks |
| ||
Pack quantity | 1 pcs. | ||
Electrical connection – plug | |||
Connection | Connector: 1 x M12 |