Product characteristics | |||
---|---|---|---|
Electrical design | NAMUR | ||
Output function | 2 x normally closed | ||
Sensing range [mm] | 4 | ||
Housing | rectangular | ||
Dimensions [mm] | 40 x 26 x 26 | ||
Electrical data | |||
Connection to switching amplifiers | yes | ||
Switching amplifiers | connection to certified intrinsically safe circuits with the max. values: U = 15 V / I = 50 mA / P = 120 mW | ||
Nominal voltage DC [V] | 8.2; (1kΩ) | ||
Supply voltage DC [V] | 7.5…15 | ||
Current consumption [mA] | < 1; (disabled; conductive: > 2,1) | ||
Protection class | III | ||
Outputs | |||
Electrical design | NAMUR | ||
Output function | 2 x normally closed | ||
Switching frequency DC [Hz] | 1800 | ||
Detection zone | |||
Sensing range [mm] | 4 | ||
Real sensing range Sr [mm] | 4 ± 10 % | ||
Accuracy / deviations | |||
Correction factor | steel: 1 / stainless steel: 0.7 / brass: 0.5 / aluminium: 0.4 / copper: 0.3 | ||
Hysteresis [% of Sr] | 1…15 | ||
Switch point drift [% of Sr] | -10…10 | ||
Operating conditions | |||
Ambient temperature [°C] | -20…80 | ||
Protection | IP 67 | ||
Safety classification | |||
Max. internal capacitance [nF] | 140; (per intrinsically safe circuit) | ||
Max. internal inductance [µH] | 130; (per intrinsically safe circuit) | ||
Mechanical data | |||
Weight [g] | 67.5 | ||
Housing | rectangular | ||
Mounting | non-flush mountable | ||
Dimensions [mm] | 40 x 26 x 26 | ||
Materials | housing: PBT; cover: PC | ||
Tightening torque [Nm] | 0.6…1.5; (Lock nut) | ||
Displays / operating elements | |||
Display |
| ||
Remarks | |||
Pack quantity | 1 pcs. | ||
Electrical connection | |||
Connection | Connector: 1 x M12 |