Product characteristics | |||
---|---|---|---|
Output function | 2 x normally closed | ||
Sensing range [mm] | 4 | ||
Housing | rectangular | ||
Dimensions [mm] | 33 x 60 x 92 | ||
Electrical data | |||
Connection to switching amplifiers | yes | ||
Switching amplifiers | connection to certified intrinsically safe circuits with the max. values: U = 15 V / I = 50 mA / P = 120 mW | ||
Operating voltage [V] | 8.2 DC; (1kΩ) | ||
Supply voltage DC [V] | 7.5…15; (when used outside the hazardous area) | ||
Current consumption [mA] | < 1; (disabled; conductive: > 2,1) | ||
Protection class | III | ||
Actuator wiring | connection to certified intrinsically safe circuits of solenoid valves with the max. values: U = 28 V / I = 250 mA / P = 750 mW (bis 40 °C) / P = 650 mW (bis 70 °C); (When used in gas atmospheres (group II) the following maximum values are permitted: U = 28 V / P = 1,1 W; These values must not be exceeded.) | ||
Outputs | |||
Output function | 2 x normally closed | ||
Switching frequency DC [Hz] | 500 | ||
Overload protection | yes | ||
Detection zone | |||
Sensing range [mm] | 4 | ||
Real sensing range Sr [mm] | 4 ± 10 % | ||
Operating distance [mm] | 0…3.25 | ||
Accuracy / deviations | |||
Correction factor | steel: 1 / stainless steel: 0.7 / brass: 0.5 / aluminium: 0.4 / copper: 0.3 | ||
Hysteresis [% of Sr] | 1…15 | ||
Switch point drift [% of Sr] | -10…10 | ||
Operating conditions | |||
Ambient temperature [°C] | -25…70 | ||
Protection | IP 65; IP 67 | ||
Safety classification | |||
Max. internal capacitance [nF] | 60; (per intrinsically safe circuit) | ||
Max. internal inductance [µH] | 130; (per intrinsically safe circuit) | ||
Mechanical data | |||
Weight [g] | 220.5 | ||
Housing | rectangular | ||
Mounting | non-flush mountable | ||
Dimensions [mm] | 33 x 60 x 92 | ||
Materials | housing: PA | ||
Displays / operating elements | |||
Display |
| ||
Accessories | |||
Accessories (supplied) |
| ||
Remarks | |||
Remarks |
| ||
Pack quantity | 1 pcs. | ||
Electrical connection | |||
terminal strip in the terminal chamber: …2.5 mm²; Cable gland: M20 X 1.5 | |||
Electrical connection – socket | |||
Connection | Connector: 1 x M12 |