Product characteristics | |||||||||
---|---|---|---|---|---|---|---|---|---|
Number of inputs and outputs | Number of digital outputs: 4 | ||||||||
Probe length L [mm] | 100…1600 | ||||||||
Process connection | G 3/4 external thread | ||||||||
Application | |||||||||
Special feature | Gold-plated contacts | ||||||||
Media | Liquids | ||||||||
Dielectric constant of the medium | ≥ 1,8; (for media with a dielectric constant of 1.8…5 (e.g. oils), a coaxial pipe is needed for operation) | ||||||||
Recommended media | water; hydrous media; oils; oil-based media | ||||||||
Cannot be used for | See the operating instructions, chapter “Function and features”. | ||||||||
Medium temperature [°C] | -25…80; (90 < 1 h) | ||||||||
Tank pressure [bar] | -1…16 | ||||||||
MAWP (for applications according to CRN) [bar] | 16 | ||||||||
Electrical data | |||||||||
Operating voltage [V] | 18…30 DC | ||||||||
Current consumption [mA] | < 30 | ||||||||
Protection class | III | ||||||||
Reverse polarity protection | yes | ||||||||
Power-on delay time [s] | < 3 | ||||||||
Inputs / outputs | |||||||||
Number of inputs and outputs | Number of digital outputs: 4 | ||||||||
Outputs | |||||||||
Total number of outputs | 4 | ||||||||
Output signal | switching signal; IO-Link | ||||||||
Electrical design | PNP | ||||||||
Number of digital outputs | 4 | ||||||||
Output function | normally open / normally closed; (parameterisable) | ||||||||
Max. voltage drop switching output DC [V] | 2.5 | ||||||||
Permanent current rating of switching output DC [mA] | 200 | ||||||||
Short-circuit protection | yes | ||||||||
Type of short-circuit protection | thermal, pulsed | ||||||||
Overload protection | yes | ||||||||
Measuring/setting range | |||||||||
Probe length L [mm] | 100…1600 | ||||||||
Active range A [mm] | L-40; (when set to oil and oil based media: L-60) | ||||||||
Inactive range I1 / I2 [mm] | 30 / 10; (when set to oil and oil based media: 30 / 30) | ||||||||
Sampling rate [Hz] | 4 | ||||||||
Setting range | |||||||||
Set point SP [mm] | ≥ 15…L-30 | ||||||||
Note on setpoint SP |
| ||||||||
Reset point rP [mm] | ≥ 10…L-35 | ||||||||
Note on reset point rP |
| ||||||||
In steps of [mm] | 5 | ||||||||
Hysteresis [mm] | > 5 | ||||||||
Accuracy / deviations | |||||||||
Repeatability [mm] | ± 5 | ||||||||
Measuring error [mm] | ± 7 | ||||||||
Offset error [mm] | 5 | ||||||||
Resolution [mm] | 1 | ||||||||
Temperature drift per 10 K | ± 0.2 % | ||||||||
Interfaces | |||||||||
Communication interface | IO-Link | ||||||||
Transmission type | COM2 (38,4 kBaud) | ||||||||
IO-Link revision | 1.1 | ||||||||
SDCI standard | IEC 61131-9 CDV | ||||||||
Profiles | no profile | ||||||||
SIO mode | yes | ||||||||
Required master port type | A | ||||||||
Process data analogue | 1 | ||||||||
Process data binary | 4 | ||||||||
Min. process cycle time [ms] | 2.3 | ||||||||
Supported DeviceIDs |
| ||||||||
Operating conditions | |||||||||
Ambient temperature [°C] | -25…60 | ||||||||
Storage temperature [°C] | -40…85 | ||||||||
Protection | IP 67 | ||||||||
Mechanical data | |||||||||
Weight [g] | 449.6 | ||||||||
Materials | stainless steel (1.4301 / 304); stainless steel (1.4404 / 316L) ; FKM; PBT; PC; PEI; TPE-V | ||||||||
Materials (wetted parts) | stainless steel (1.4305 / 303); probe connection: stainless steel (1.4435 / 316L); PTFE; FKM; Sealing: NBR reinforced fibre | ||||||||
Process connection | G 3/4 external thread | ||||||||
Displays / operating elements | |||||||||
Display |
| ||||||||
Remarks | |||||||||
Notes | For 8-pole sockets the core colours are not standardised.; Please note the wiring of the sensor and the sockets (see data sheet).; Please see the technical note under “Downloads” | ||||||||
Pack quantity | 1 pcs. | ||||||||
Electrical connection | |||||||||
Connection | Connector: 1 x M12; Contacts: gold-plated |