Product characteristics | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Output signal | switching signal | ||||||||||
Measuring range [bar] | 0…100 | ||||||||||
Process connection | threaded connection G 1/4 internal thread | ||||||||||
Application | |||||||||||
Special feature | Gold-plated contacts | ||||||||||
Application | for industrial applications | ||||||||||
Media | liquids and gases | ||||||||||
Conditionally suitable for | use in gases at pressures > 25 bar only on request | ||||||||||
Medium temperature [°C] | -25…80 | ||||||||||
Min. bursting pressure [bar] | 650 | ||||||||||
Pressure rating [bar] | 300 | ||||||||||
Type of pressure | relative pressure | ||||||||||
Electrical data | |||||||||||
Operating voltage [V] | 18…30 DC | ||||||||||
Current consumption [mA] | < 90 | ||||||||||
Min. insulation resistance [MΩ] | 100; (500 V DC) | ||||||||||
Protection class | III | ||||||||||
Reverse polarity protection | yes | ||||||||||
Power-on delay time [s] | 0.2 | ||||||||||
Integrated watchdog | yes | ||||||||||
Inputs / outputs | |||||||||||
Number of inputs and outputs | Number of digital outputs: 2 | ||||||||||
Inputs | |||||||||||
Analogue input (current) [mA] | 0…20 | ||||||||||
Max. load [Ω] | 300 | ||||||||||
Analogue input (voltage) [V] | 0…10 | ||||||||||
Min. load resistance [Ω] | 90000 | ||||||||||
Outputs | |||||||||||
Total number of outputs | 2 | ||||||||||
Output signal | switching signal | ||||||||||
Electrical design | PNP/NPN | ||||||||||
Number of digital outputs | 2 | ||||||||||
Output function | normally open / normally closed; (parameterisable) | ||||||||||
Max. voltage drop switching output DC [V] | 2 | ||||||||||
Permanent current rating of switching output DC [mA] | 250 | ||||||||||
Switching frequency DC [Hz] | < 170 | ||||||||||
Short-circuit protection | yes | ||||||||||
Type of short-circuit protection | pulsed | ||||||||||
Overload protection | yes | ||||||||||
Measuring/setting range | |||||||||||
Measuring range [bar] | 0…100 | ||||||||||
Set point SP [bar] | -24.6…100 | ||||||||||
Note on setpoint SP |
| ||||||||||
Reset point rP [bar] | -25…99.6 | ||||||||||
Note on setpoint SP |
| ||||||||||
In steps of [bar] | 0.2 | ||||||||||
Accuracy / deviations | |||||||||||
Characteristics deviation [% of the final value] | < ± 0,6 | ||||||||||
Temperature drift per 10 K | < ± 0.3 | ||||||||||
Characteristics deviation analogue input | < ± 0.3 | ||||||||||
Temperature drift analogue input per 10 K | < ± 0.1 | ||||||||||
Temperature drift analogue input [°C] | 0…80 | ||||||||||
Response times | |||||||||||
Response time [ms] | < 3 | ||||||||||
Delay time programmable dS, dr [s] | 0, 0,1…50 | ||||||||||
Damping for the switching output dAP [s] | 0…4 | ||||||||||
Software / programming | |||||||||||
Adjustment of the switch point | programming button | ||||||||||
Parameter setting options | hysteresis / window; normally open / normally closed; switching logic; current/voltage input; Damping; adaptation of displayed values; display can be rotated and switched off; Display unit | ||||||||||
Operating conditions | |||||||||||
Ambient temperature [°C] | -25…80 | ||||||||||
Storage temperature [°C] | -40…100 | ||||||||||
Protection | IP 67 | ||||||||||
Mechanical data | |||||||||||
Weight [g] | 291.5 | ||||||||||
Materials | stainless steel (1.4305 / 303); PBT; PC; PA; FKM | ||||||||||
Materials (wetted parts) | stainless steel (1.4305 / 303); ceramics; FKM | ||||||||||
Min. pressure cycles | 100 million | ||||||||||
Process connection | threaded connection G 1/4 internal thread | ||||||||||
Restrictor element integrated | no (can be retrofitted) | ||||||||||
Displays / operating elements | |||||||||||
Display |
| ||||||||||
Display unit | bar; psi; MPa | ||||||||||
Remarks | |||||||||||
Pack quantity | 1 pcs. | ||||||||||
Electrical connection | |||||||||||
Connection | Connector: 1 x M12; Contacts: gold-plated |