Electrical data | |||||
---|---|---|---|---|---|
Frequency AC [Hz] | 47…64 | ||||
Operating voltage tolerance [%] | 15…20 | ||||
Nominal voltage AC [V] | < 400 | ||||
Input voltage range AC [V] | 380…480 | ||||
Output voltage DC [V] | 24…28 | ||||
Protection class | I; (IEC 61140) | ||||
Overvoltage protection | yes; (< 32 DC) | ||||
Output voltage [V] | adjustable; output voltage to SELV, PELV | ||||
Max. output current at min. output voltage [A] | 40 | ||||
Max. output current at max. output voltage [A] | 34.3 | ||||
Max. output current peak at min. output voltage [A] | 60 | ||||
Max. output current peak at max. output voltage [A] | 51.5 | ||||
Output power (permanent) [W] | 960 | ||||
Output power (peak) [W] | 1440 | ||||
Note on output power (peak) |
| ||||
Power factor (nominal voltage 400 V AC / 50 Hz) | 0.88 | ||||
Note on power factor (nominal voltage 400 V AC / 50 Hz) |
| ||||
Power factor (nominal voltage 480 V AC / 50 Hz) | 0.9 | ||||
Note on power factor (nominal voltage 480 V AC / 50 Hz) |
| ||||
Power reserve [%] | 50 | ||||
Number of output circuits | 1 | ||||
Max. residual ripple [mV] | 100 | ||||
Switch-on peak current (nominal voltage 400 V AC / 60 Hz) [A] | 4.5 | ||||
Switch-on peak current (nominal voltage 480 V AC / 50 Hz) [A] | 4.5 | ||||
Inrush current limitation | yes | ||||
Efficiency (nominal voltage 400 V AC / 60 Hz) [%] | 95.3 | ||||
Efficiency (nominal voltage 480 V AC / 50 Hz) [%] | 95.2 | ||||
External input protection | ≥ B-6 A / ≥ C-6 A | ||||
Derating [W/K] | 24 (60…70 °C) | ||||
Mains buffering time (nominal voltage 400 V AC / 60 Hz) [ms] | 25 | ||||
Mains buffering time (nominal voltage 480 V AC / 50 Hz) [ms] | 25 | ||||
Input current (nominal voltage 400 V AC / 60 Hz) [A] | 1.65 | ||||
Input current (nominal voltage 480 V AC / 50 Hz) [A] | 1.35 | ||||
Power loss (nominal voltage 400 V AC / 60 Hz) [W] | 47.3 | ||||
Power loss (nominal voltage 480 V AC / 50 Hz) [W] | 48.4 | ||||
Back feeding protection [V] | 35 | ||||
Outputs | |||||
Short-circuit proof | yes | ||||
Overload protection | yes | ||||
Overload performance | output current constant | ||||
Type DC-OK signal | relay output | ||||
Reliability of the DC OK signal | 60 V DC (0.3 A) / 30 V DC (1 A) / 30 V AC (0.5 A) | ||||
Operating conditions | |||||
Ambient temperature [°C] | -25…70 | ||||
Note on ambient temperature |
| ||||
Storage temperature [°C] | -40…85 | ||||
Max. relative air humidity [%] | 95; (IEC 60068-2-30) | ||||
Protection | IP 20; (EN 60529) | ||||
Degree of soiling | 2; (IEC 62103: conductive soiling not permitted) | ||||
Mechanical data | |||||
Weight [g] | 1754.5 | ||||
Type of mounting | rail; (TH35 (EN 60715)) | ||||
Dimensions [mm] | 124 x 110 x 130.7 | ||||
Materials | steel sheet | ||||
Displays / operating elements | |||||
Display |
| ||||
Remarks | |||||
Remarks |
| ||||
Pack quantity | 1 pcs. | ||||
Electrical connection | |||||
Connection | screw terminals: |