Product characteristics | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Number of inputs and outputs | Number of digital outputs: 2; Number of analogue outputs: 1 | ||||||||||
Measuring range [ml/min] | 1…200 | ||||||||||
Process connection | threaded connection G 1/8 | ||||||||||
Application | |||||||||||
Media | water; hydrous media | ||||||||||
Medium temperature [°C] | 0…60 | ||||||||||
Pressure rating [bar] | 10 | ||||||||||
Electrical data | |||||||||||
Operating voltage [V] | 19…30 DC; (according to EN 50178 SELV/PELV) | ||||||||||
Current consumption [mA] | < 110 | ||||||||||
Protection class | III | ||||||||||
Reverse polarity protection | yes | ||||||||||
Power-on delay time [s] | 5 | ||||||||||
Inputs / outputs | |||||||||||
Number of inputs and outputs | Number of digital outputs: 2; Number of analogue outputs: 1 | ||||||||||
Outputs | |||||||||||
Total number of outputs | 2 | ||||||||||
Output signal | switching signal; analogue signal; pulse signal; (configurable) | ||||||||||
Electrical design | PNP | ||||||||||
Number of digital outputs | 2 | ||||||||||
Output function | normally open / normally closed; (parameterisable) | ||||||||||
Max. voltage drop switching output DC [V] | 2 | ||||||||||
Permanent current rating of switching output DC [mA] | 250; (per output) | ||||||||||
Number of analogue outputs | 1 | ||||||||||
Analogue current output [mA] | 4…20; (scalable) | ||||||||||
Max. load [Ω] | 500 | ||||||||||
Pulse output | consumed quantity meter | ||||||||||
Short-circuit protection | yes | ||||||||||
Type of short-circuit protection | pulsed | ||||||||||
Short-circuit proof | yes | ||||||||||
Overload protection | yes | ||||||||||
Measuring/setting range | |||||||||||
Measuring range [ml/min] | 1…200 | ||||||||||
Display range [ml/min] | 0…240 | ||||||||||
Set point SP [ml/min] | 6…200 | ||||||||||
Reset point rP [ml/min] | 1…195 | ||||||||||
Analogue start point ASP [ml/min] | 0…150 | ||||||||||
Analogue end point AEP [ml/min] | 50…200 | ||||||||||
In steps of [ml/min] | 1 | ||||||||||
Measuring dynamics | 1:200 | ||||||||||
Volumetric flow quantity monitoring | |||||||||||
Pulse value | 0.1…2000000000 ml | ||||||||||
In steps of | 0.1…1000000 ml | ||||||||||
Pulse length [s] | 0,0125…2 | ||||||||||
Temperature monitoring | |||||||||||
Measuring range [°C] | 0…60 | ||||||||||
Display range [°C] | 0…72 | ||||||||||
Set point SP [°C] | 1.8…60 | ||||||||||
Reset point rP [°C] | 0.3…58.5 | ||||||||||
Analogue start point [°C] | 0…45 | ||||||||||
Analogue end point [°C] | 15…60 | ||||||||||
In steps of [°C] | 0.1 | ||||||||||
Accuracy / deviations | |||||||||||
Flow monitoring | |||||||||||
Accuracy (in the measuring range) | ± (15 % MW + 2 % MEW); (The values apply for the following conditions:; Application: water; Medium temperature: 20 °C; Ambient temperature: 22…28 °C; unit with mounted flow conditioner) | ||||||||||
Repeatability | ± 3% MW | ||||||||||
Response times | |||||||||||
Flow monitoring | |||||||||||
Response time [s] | 0.3; (dAP = 0; for rising flow; for falling flow) | ||||||||||
Damping for the switching output dAP [s] | 1…5 | ||||||||||
Damping for the switching output dAP in steps [s] | 0 – 0,2 – 0,4 – 0,6 – 0,8 – 1…5 | ||||||||||
Software / programming | |||||||||||
Parameter setting options | Flow monitoring; quantity meter; Preset counter; Temperature monitoring | ||||||||||
Operating conditions | |||||||||||
Ambient temperature [°C] | 0…60 | ||||||||||
Storage temperature [°C] | -25…85 | ||||||||||
Protection | IP 65 | ||||||||||
Mechanical data | |||||||||||
Weight [g] | 453 | ||||||||||
Materials | stainless steel (1.4404 / 316L); PC; PBT-GF20; POM; NBR | ||||||||||
Materials (wetted parts) | stainless steel (1.4404 / 316L); FKM | ||||||||||
Process connection | threaded connection G 1/8 | ||||||||||
Displays / operating elements | |||||||||||
Display |
| ||||||||||
Remarks | |||||||||||
Remarks |
| ||||||||||
Pack quantity | 1 pcs. | ||||||||||
Electrical connection | |||||||||||
Connection | Connector: 1 x M12 |